top of page
Drainage System Design

An efficient plumbing system starts with a design that saves water and energy resources. A good design incorporates short runs between plumbing fixtures and uses state-of-the art materials. A plumbing design must include two systems: the system that supplies water and the system that gets rid of waste. Before you begin designing a house for plumbing, drain, waste and vent systems, you must follow local building codes to ensure design compliance.

A Plumbing designer should know the basic plumbing principles and standards of plumbing materials. Avoid any plumbing plans that requires the plumber to weaken the building structure.

Planning Drainage, Waste and Vent System
Materials

Drainage piping shall be HDPE, PVC, ABS, uPVC, Cast Iron, Galvanized Steel, Lead, Copper, Brass, Stainless Steel, extra-strength vitrified clay pipe, or other approved materials having a smooth uniform bore. In general, materials must be free from defects and meet the standards of the building department.

Table 3.5 : Materials for Sanitary Waste & Drain System (NSPC-2006)

Table 3.6: Materials for Sanitary Vent Piping (NSPC-2006)

Table 3.7: Material for Storm Drainage (NCPS-2006)

Table 3.8 : Materials for Foundation and Sub-Soil Drainage (NSPC-2006)

main-qimg-f215adfe9d19a8434c6175c7c27530

Joints and Connections
Joints and connections in the plumbing system shall be gas tight and watertight for the pressure required by test, with the exceptions of those of perforated or open joint piping that are installed for the purpose of collecting and conveying ground or sepage water to the underground storm drains.
Different types of joints used in plumbing system are : Threaded joints, Brazed joints, Soldered joints, Welded joints, Flanged joints, Compression joints, Grooved joints etc .

DSC04858-BANNER-v2__FillWzU2MCwyMjBd.jpg

Changes in Direction of Drainage Flow


(a) Changes in direction of drainage piping shall be made by appropriate used of approved fittings and shall be angle of angles presented by 22.5⁰ (1/16), 45⁰ (1/8), 60⁰ (1/6) or other approved fittings of equivalent sweep.

(b) Horizontal drainage lines, connecting with a vertical stack, shall enter through  combination of wye branch and 45⁰ bend or 45⁰ wye branch fittings.

(c) Vertical drainage lines connecting with other horizontal drainage lines shall enter through 45⁰ wye branch or combination of wye and 45⁰ bend.

Change in Direction fittings.jpg

Fixture Traps


(a) Fixture traps create a liquid seal that prevents drainage system odors, gases and even vermin (wild animals carrying disease) from entering the building through the fixtures.

(b) Fixture trap size shall be sufficient to drain the fixture rapidly and in no case less than given in Table 5.2 (NSPC). No trap shall be larger than the drainage pipe into which it discharges.

(c) Fixture traps shall be self-scouring and shall have no interior partitions except where such traps are integral with the fixture or where corrosion resitant materials of plastic or glass are used. Solid connections, slip joints, or couplings may be used on the trap inlet, trap outlet, or within the trap seal
.
(d) Each fixture traps shall have a liquid seal of not less than 2" and not more than 4".

(Table 5-2 : MINIMUM SIZE OF NON-INTEGRAL TRAPS (NSPC)

Fixture Traps.jpg

Cleanouts


(a) A drain cleanout provides access to main sewer line and is located outside of building or high level in ceiling inside toilets

(b) There are two basic types of code-approved cleanouts; conventional cleanouts and manholes. Conventional cleanouts with removable plugs are required on drainage pipes within a building or on a private sewer.

(c) Manholes serve as junctions to join one or more sewer lines. They allow access to inspect and clear the lines of solids that accumulate there. Manholes are common in private sewage that serve several large buildings. Install manholes at every change in grade, change in direction, and junction of two or more sewers. And don't exceed 300 feet between manholes.

(d) Provide a cleanout on the upper terminal of each horizontal drainage pipe.

(e) A cleanout shall be provided near the base of each vertical waste or soil stack 6" above FFL.

(f) Cleanouts must be easily accessible for easy cleaning.

(g) Cleanouts shall be installed at change of direction in drainage piping with 60⁰, 70⁰ and 90⁰ fittings. Cleanouts shall not be required where changes of direction are made with one or more 22.5⁰ or 45⁰ fittings.

(h) Cleanouts shall be provided for concealed piping in wall or floor.

(i) Cleanouts shall be installed so that it opens in the direction of the flow of the drainage line or at right angles thereto.

(j) Cleanout sizes shall conform with Table 5.4.9 (NSPC).

(k) Cleanouts on 3" or larger pipes shall be so installed that there is a clearance of not less that 18" for the purpose of rodding. Cleanouts smaller than 3" shall be so installed that there is a 12" clearance for rodding.

Cleanout Requirements.jpg

Slope of Horizontal Drainage Piping


(a) Horizontal drainage piping shall be installed in uniform alignments at uniform slopes not less than 1/4" per foot (20.9 mm/m) two percent (2%) for 2" pipe size and smaller and less than 1/8" per foot (10.9 mm/m) or one percent (1%) for 3" pipe size and larger. (Refer to NSPC for slope of drainage pipes)
(b) Where conditions do not permit building drains and sewer to be laid with slope as great as that specified, a lesser slope may be permitted by the Authority Having Jurisdiction.

(c) Wherever practicable, all plumbing fixtures shall be drained to public sewer or private sewer disposal system by gravity.

Slope of pipes.png

Vents and Venting
(a) Each plumbing fixture trap shall be protected against siphonage and back pressure, and air circulation shall be ensured throughout all parts of the drainage system by means of vent pipes.

(b) Vent pipes supply fresh air to each plumbing fixture in the house, which helps the system move water through the drainage pipes each time a toilet is flushed or a sink is drained. Vents also prevent sewer gases from entering the home and all wastewater gas and ador to escape.

(c) Vent pipes shall terminate not less than 6" above the roof, measured from the highest point where the vent intersects the roof.

(d) Vent terminals shall not be located where vapors can enter the building. No vent terminal shall be located directly beneath any door, window or other ventilating opening of a building.

(e) Vent and branch vent pipe shall be free from drops and sags and be sloped and connected as to drain by gravity to the drainage system.

(f) Every vent shall rise vertically to a minimum of 6" above the flood level of the rim of the fixture being served before connecting to another vent.

(g) Never locate vent pipes in stairways or hoistways.

Vent Pipe.png

Grease Interceptors


(a) In commercial buildings where food is processed, prepared or served, grease interceptors shall be installed in a waste line. If not, the accumulated grease will clog the drainage pipes. 

(b) Use an inside interceptor for small restaurants or other businesses generating minor amount of grease. It may be floor mounted or installed below the floor.

(c) Larger restaurants or other businesses generating sizable grease accumulating require interceptors located outside of the building. They need a retention time of 2.5 hours. Most large interceptors are made of precast or poured-in-place concrete.

(d) Place each grease interceptor where there's easy access for inspection, cleaning and removal of intercepted grease.

Grease Interceptor -Typical Installation
Grease Interceptor -inside.jpg
Grease Interceptor -Outside.jpg

Gasoline, Oil and Sand Interceptors
(a) We need to provide interceptors to keep gasoline, grease, oil and sand out of sanitary drainage.

(b) Anyplace where motor vehicles are repaired and floor drainage is provided.

(c) Anyplace where motor vehicles are commercial washed.

(d) Anyplace where oil, gasoline or their volatile liquids can be discharged into the sanitary drainage.

(e) Any factory which has only or flammable wastes from storage, maintenance, repair or testing processes.

Sand Interceptors.jpg
Oil Interceptors.jpg

Neutralizing Tanks
Corrosive liquids, spent acids and other chemicals might damage or destroy a DWV drainage system or create noxious or toxic fumes. This waste must pass through a properly designed dilution or neutralizing tank. The tak must automatically provide enough water to dilute the corrosive liquids until they are not damaging to the drainage systems.

Neuralizing tank typical.jpg
ATS-Acid-Neutralization-Tank.png

Indirect Waste Piping and Special Wastes
(a) A special waste pipe including oil, sand, grease, glass and storm water that does not connect directly with the drainage system but that discharges into the drainage system through an air break or air gap into a trap, fixture, receptor or interceptor are called indirect waste piping.

(b) Refrigerator coils, walk-in freezers, ice boxes, ice-making machines and bar sinks need indirect waste pipes.

(c) We can use either an air gap or air break as the indirect waste connection. The air gap is the unobstructed vertical distance between the waste pipe outlet and the flood level rim of the receptacle. Vertical distance shall be twice the diameter of the drain it serves.

(d) Air break drainage is a physical separation, usually a low inlet into the indirect waste receptor.

Air Gap.jpg
Air Break.jpg

Air Conditioning Condensate Drains


(a) When air conditioning units are located on the roof, waste may discharge on to the roof and into the roof drain.

(b) When an air conditioning unit is centrally located below the roof of a building, it may indirectly connect to a rain leader pipe. Drainage from an air handling equipment's room must be by indirect means.

(c) The main condensate drain line in a multi-story building may receive the discharge from many air conditioning units. Each individual unit must be trapped.

(d) Some codes require a vent in the main drain line above the highest connection.

Condensate Drains.jpg

Storm Drainage Systems
(a) The storm drainage system carries rainwater to a legal disposal point. It includes roof drain, area drains, catch basins, gutters, leaders, building storm drains, building storm sewers and ground surface storm sewers.

(b) You must provide a strainer where roof surface drain into the inlet of an inside leader. The strainer cover must extend at least 4" above the roof surface.

(c) Roof drains must be made of cast iron , copper, lead, or some other approved corrosion resistant materials.

(d) Traps are not required for regular storm water drains connected to a storm drainage system.

RA Drain.JPG

Septic Tank System
(a) A septic tank is simply a water tight receptacle for the sewage discharged by a building drainage system. It separates the solid from the liquid wastes before the treated liquid seeps into the ground.

(b) The tank should be large enough to hold approx. 24 hours of an anticipated flow. This retention period gives the bacterial action time to digest the solids.

(c) The new sewage entering the tank also forces an equal amount of treated liquid out through the outlet tee of the septic tank.

(d) When the bacterial process is complete, the remaining solids settle to the bottom as sludge. Lighter undigested particles rise and form a scum on top of the liquid contents. Over a period of years, the sludge and scum builds up and reduce the tank efficiency. Periodic cleaning keeps it working effectively.

CONSTRUCTION OF TYPICAL SEPTIC TANK

Floor Drain and Trench Drain
A floor drain is a plumbing fixture that is installed in the floor of a structure, mainly designed to remove any standing water near it. They are usually round, but can also be square or rectangular.

Floor drains shall have a water seal of not less than 2 inches and shall be fitted with a removable strainer. The free open area of strainers shall be at least 2/3 of the cross-sectional area of the nominal drain outlet size. 

Floor drains and their branch piping shall be sized on the basis of their normal, expected flow rate, shall be not less than 2" nominal size. If provided for emergency showers and eyewash stations, floor drains and their fixture drain branches shall be sized for GPM discharge capacity of the shower or eyewash, but the drainage fixture unit (DFU) loading on the sanitary drainage system shall be zero (0,0 DFU).

Floor drains shall be installed in the following areas:

1) Toilet rooms containing either two or more water closets or wall hung urinals or a combination of one or more water closets and wall hung urinals, except in a dwelling unit.

2) Commercial kitchens.

3) Common laundry rooms in commercial buildings and buildings having more than two dwelling units.

(Floors shall be sloped to floor drains where drainage occurs).

floor drains.jpg
FD-5030S.jpg
Toilet Design -1 Plan_Page_1.png
Toilet Design -1 Iso_Page_1.png
Scan_0001.jpg
Scan_0002.jpg
Scan_0003.jpg
14040 - 308 -FIRST FLOOR PLAN-DRAIN-Mode
bottom of page